Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

!
A
EN
66

Maintenance

Maintenance
Warning!
Improper maintenance can result in life-threatening danger and risk of injury:
The owner is responsible for correct installation and functional inspection of the
escape door. According to DIN EN 1125 and DIN EN 179 an escape door must be
inspected at least once per month for safe function and the inspection results
must be recorded. Requirements established by inspection authorities must be
complied with,
Attention!
Property damage and impaired function due to incorrect lubrication: No
lubricants may be applied to the lock or sprayed into the lock. Apply a fine film of
silicon grease to the latch sliding surface if necessary.
Conducting maintenance tasks
1. Ensure that all parts of the lock (lock, door fitting and striking plate) work
safely.
2. Ensure that all parts of the lock are clean in order to prevent functional
impairment.
3. Ensure that all components of the system still correspond to the list of
approved components originally supplied with the system.
4. Ensure that all operating elements are mounted safely.
5. Using a dynamometer, ensure that the actuating force to release the escape
door lock has not changed significantly (max. 10%) since the initial installa-
tion.
6. When working on a fire door, ensure that it has not been modified since the
initial installation.
Maintenance

Publicité

Table des Matières
loading

Table des Matières