When finishing the connection and pressurization operations of the hydraulic
1
system, execute a tightness test at a higher pressure than the standard one, in
order to avoid water leaks during the regular use of the unit.
2
MAX. TIGHTENING TORQUE FOR THE CONNECTION OF THE EURAPO VALVE
KIT IS 20 Nm
3
If the control valves are not supplied by EURAPO, EURAPO is not responsible for any
malfunction or wrong electrical connection referred to the valves.
4

6.6 ELECTRICAL CONNECTIONS

5
Before making any electrical connection, verify the compatibility between
power supply and the technical features of the fancoil and/or of the other
6
accessories to be connected to the unit. These features are illustrated in
the identification plate, located on one side of the fancoil (Fig. 1).
7
The conductors of the power supply cables of the air-handling unit and its accessories must be
flexible cables and have the nominal section shown in the following table:
8
Nominal power of the unit (A)
9
10
+
In the power supply system to the fan coil and its accessories, a double-pole
switch must be foreseen with a minimum distance of 3 mm between contacts
in each poles.
For a correct management and use of the fan coil and its accessories, the use of an
EURAPO microprocessor control or OMNIBUS control is suggested. The control has to be
chosen according to the requirements of the installation.
34
≤3
>3 and ≤6
>6 and ≤10
>10 and ≤16
>16 and ≤25
>25 and ≤32
>32 and ≤50
>50 and ≤63
Nominal section (mm²)
from 0,5 to 0,75
from 0,75 to 1
from 1 to 1,5
from 1,5 to 2,5
from 2,5 to 4
from 4 to 6
from 6 to 10
from 10 to 16