Transport And Warehouse Storage - EURAPO Sigma Manuel D'utilisation Et Installation

110-328, 110-218
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Fig. 1 Label on fancoil
• Insulation class: I. - Protection grade: IPX0
• Protection grade of the motor: IP20.
• Technical features of the heat exchanger:
-
Max pressure of the hot or cold water for water fan coil:
1600 kPa - with valves: 1000 kPa.
-
Min pressure of the hot or cold fluid: It is the one indicated by the designer/installer for
the correct functioning of the system.
Min/max water temperature: 5/85 °C.
-
-
Hardness of water into the heat exchanger: It is the one indicated by the de-
signer/installer for the correct functioning of the system.
• Technical features of the fan motor:
-
With each fan coil unit there is the possibility to have 6 different air volumes and
the relevant electric motor connections accordingly to the use requirements. The
standard electrical connection has a triad of speeds: MIN-MED-MAX (L-5, L-3,
L-2). The relevant nominal air capacities are indicated in the Encl. 3 and they are
referred to standard fan coil units, with clean filters, at the temperature of 20 °C,
at sea level and without external static pressure.
-
The electric motor is provided with internal thermic protection; it is a monophasic
motor with capacitor permanently inserted.

5. TRANSPORT AND WAREHOUSE STORAGE

All fan coils with casing are wrapped in a plastic bag to protect the unit from dust and scratches;
they are then packed in a cardboard box to allow an easy and safe manoeuvrability and to
minimise risks due to incorrect handling. Fan coil units without casing are directly packed in a
carton box. On the carton box, symbols showing how to stock the goods correctly are printed.
A label on it provides complete information on its contents.
If fan coils are stored in the warehouse, do not exceed the following stacking limitations:
MODELS WITH CASING
Stacking position: VERTICAL
Max. no. of units that may be stacked: 3
MODELS WITHOUT CASING (CONCEALED MODELS):
Stacking position: HORIZONTAL
Max. no. of units that may be stacked: 7