Even though the units have been properly protected to withstand adverse conditions,
1
we recommend that they be kept under the following ambient conditions if stored in the
warehouse for long periods of time: Temperature: min. –5 °C, max. 50 °C; relative humidity:
less than 80%.
2
When receiving the goods, please open the shipping carton, to make sure that all
components are present and in good condition. Any damage must be immediately
communicated to the shipping agent, and our service department must be notified
3
immediately if any material is missing.

6. INSTALLATION

4
6.1 PRESCRIPTIONS AND OBLIGATIONS
5
Each operation for installation and/or maintenance must be executed by qualified
personnel only, by respecting the safety norms and the installation rules of the
Country where the fan coil is installed. EURAPO s.r.l. refuses every responsibility
6
for any damages caused by incorrect installation or improper use of the fan coil
and its accessories. In particular, when making connections, do not use hanging,
non-standard connections or flexible tubes with unsuitable connectors. Always
7
use expansion bolts.
The positioning and the connection of the fan coil must be established from
8
the designer of the system, who has to assure the correct running of the unit by
respecting the rules and the laws in use in the Country where the unit is installed.
It is a mandatory:
9
to install the horizontal fan coil unit at least at 1,80 mt from the floor;
to use water or a mixture of water and propylene or ethylene glycol to feed the heat exchanger.
Maximum glycol content 50%.
10
Installation sites to avoid:
moist rooms or places where the unit may get in contact with water sprays (laundries,
bathrooms, etc.);
+
areas exposed to direct sunshine or too close to heating sources (lamps etc.);
rooms where the following substances might be present: flammable gas, alkaline material
or oil vapours;
positions where the air intake or air outlet might be obstructed (by shelving, furniture etc.);
in areas with risks of explosion or with severely dusty air.
The installation of the fan coil must assure:
safe use and working: the unit has not to cause any damage or danger to persons, objects or animals;
a regular air circulation in the room;
the air intake and outlet are not obstructed in any way;
the respect of the minimum space necessary for installation and maintenance operations;