Codes for parameter setting
Code
No.
Name
2
C0120 I
t switch−off
C0311
Functions for
*
special
v
applications 2
(from software
version 3.9)
Adjustment
1. Calculate C0120. This value corresponds to a motor utilisation of 100 %:
I
r
C0120 [%] +
@ 100 %
I
N
2. If you decrease C0120 on the basis of the value calculated, the monitoring already responds at
a motor utilisation < 100 %.
3. If you increase C0120 on the basis of the value calculated, the monitoring only responds at a
motor utilisation > 100 %.
The controller switches off with error OC6 if the apparent motor current is greater than the rated
motor current for a longer time.
EDK82EV113 DE/EN/FR 11.0
Possible settings
Lenze Selection
0
0
= inactive
1
0
All functions switched off
, System manual
1, 2, 4,
8, 16
1
128
Function active:
When the device is connected to the
mains, the thermal motor load is
initialised with 50 %.
The function has to be activated for
operation in UL−approved systems.
I
Rated motor current
r
I
Rated controller current at switching frequency 8 kHz
r
Safety instructions
Thermal motor monitoring
{1 %}
l
IMPORTANT
200 Reference: apparent motor
current (C0054)
Reference to active motor current
(C0056) possible, see C0310
A combination of functions can be
activated by entering the sum of
the selection values.
2
Motor overload (I
xt) tart value
Function switched−off:
When the device is connected to
the mains, the thermal motor load
is initialised with 0 % ("cold
engine")
2
95