Lenze 8200 vector Instructions De Montage page 153

Masquer les pouces Voir aussi pour 8200 vector:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Code
No.
Name
C0034*
Range of
v
setpoint
selection
(A)
Application I/O
uSEr
1 X3/1U, X3/1I
2 X3/2U, X3/2I
C0037
JOG1
C0038
JOG2
C0039
JOG3
C0050*
Output
frequency
uSEr
(MCTRL1−NOUT)
C0087
Rated motor
speed
C0088
Rated motor
current
C0089
Rated motor
frequency
C0090
Rated motor
voltage
Motor cos 
C0091
C0119
Configuration of
v
motor
temperature
monitoring (PTC
input) / earth
fault detection
EDK82EV113 DE/EN/FR 11.0
Possible settings
Lenze
Selection
0
0
Unipolar voltage 0 ... 5 V / 0 ... 10 V
1
Bipolar voltage −10 V ... +10 V
2
Current 0 ... 20 mA
3
Current 4 ... 20 mA
4
Current 4 ... 20 mA open−circuit monitored
20.00 −650.00
30.00 −650.00
40.00 −650.00
−650.00
à
300
à
0.0
50
10
à
50
à
0.40
0
0
PTC input inactive
1
PTC input active,
TRIP effected
2
PTC input active,
warning effected
3
PTC input inactive
4
PTC input active,
TRIP effected
5
PTC input active,
warning effected
Important codes for quick commissioning
{0.02 Hz}
650.00 JOG = fixed setpoint
{0.02 Hz}
650.00
{0.02 Hz}
650.00
{Hz}
650.00 Read only: Output frequency without
16000 à Device−dependent
{1 rpm}
650.0 à Device−dependent
0.1 (A)
{1 Hz}
960
500 à 230 V for 230 V controllers,
{1 V}
{0.1}
Earth fault
detection active
Earth fault
detection inactive
l
Commissioning
IMPORTANT
Observe jumper position of the
function module!
Minimum output frequency (C0010)
not effective
Reversal of rotation direction only
possible with a digital signal.
Reversal of rotation direction only
possible with a digital signal.
TRIP Sd5 at I < 4 mA
Additional fixed setpoints ðC0440
slip compensation
0.0 ... 2.0 x rated output current of the
controller
400 V for 400 V controllers
1.0 à Device−dependent
l
Configure signal output in C0415
l
If several parameter sets are
used, monitoring has to be set
separately for every parameter
set.
l
Deactivate earth fault detection if
the earth fault detection is
actuated unintentionally.
l
If the earth fault detection is
activated, the motor starts with a
delay of approx. 40 ms after
controller enable has been set.
7
153