Lenze 8200 vector Instructions De Montage page 162

Masquer les pouces Voir aussi pour 8200 vector:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

8
Troubleshooting and fault elimination
Fault elimination
Fault messages
1)
Keypad
PC
Fault
DC−bus overvoltage
OU
(message or TRIP
c
configurable in
C0310)
22
OUE
a
75
Faulty parameter
Pr
transfer via keypad
a
72
Faulty PAR1 transfer
Pr1
via keypad
a
73
Faulty PAR2 transfer
Pr2
via keypad
a
77
Faulty PAR3 transfer
Pr3
via keypad
a
78
Faulty PAR4 transfer
Pr4
via keypad
a
79
Internal fault
Pr5
a
81
Time error during
Pt5
parameter set
a
transfer
76
Error during
rSt
Auto−TRIP reset
a
85
Wire breakage,
sd5
analog input 1
a
87
Wire breakage,
sd7
analog input 2
a
1)
LECOM error number, display in Global Drive Control (GDC) parameter setting program
162
Cause
Mains voltage is too high
Braking operation
Earth leakage at motor end
All parameter sets are defective
Parameter set 1 is defective
Parameter set 2 is defective
Parameter set 3 is defective
Parameter set 4 is defective
EEPROM is defective
Data flow from keypad or PC
interrupted, e.g. keypad has been
removed during data
transmission
More than 8 error messages
within 10 minutes
Current on analog input < 4 mA
for setpoint range 4 ... 20 mA
l
Remedy
Check supply voltage
l
Increase deceleration times
l
For operation with an external
brake resistor:
– Check dimensioning,
connection and supply cable of
the brake resistor
– Increase deceleration times
Check motor supply cable and motor
for earth fault (disconnect motor
from the inverter)
Before enabling the controller, repeat
the data transfer or load the Lenze
setting
Contact Lenze
Before enabling the controller, repeat
the data transfer or load the Lenze
setting.
Dependent on the error message
Close the circuit at the analog input
EDK82EV113 DE/EN/FR 11.0

Publicité

Table des Matières
loading

Table des Matières