5
Electrical installation
Wiring
EMC−compliant wiring
PE
PE
PE
M
3~
8
9
L < 40 mm
PES
0
Mounting plate with electrically conductive surface
1
Control cable to the function module, connect the shielding to the EMC shield sheet (PES) with a surface as large
as possible
2
2−pole terminal for motor PE and motor shield
3
PE of the motor cable
4
Shield of the motor cable
5
Shielded motor cable, low−capacitance
2
(Core/core 1.5 mm
6
Shielded PTC cable or thermal contact cable
7
Connect the cable shields to the EMC shield sheet (PES) with a surface as large as possible. Use the supplied
shield clamps.
8
Star or delta connection as indicated on the motor nameplate
9
EMC cable connector (not included in the delivery package)
116
0
1
2
3
4
5
6
7
L < 500 mm
£ 75 pF/m; from 2.5 mm
2
PES
£ 100 pF/m; core/shield £ 150 pF/m)
l
PES
EDK82EV113 DE/EN/FR 11.0