1)
Keypad
PC
Fault
65
BUS−OFF
ce4
(many
a
communication
errors occurred)
66
CAN time−out
ce5
(configurable in
a
C0126)
67
System bus (CAN)
ce6
function module on
a
FIF has the
"Warning" or
"BUS−OFF" status
(configurable in
C0126)
68
Communication
ce7
error during remote
a
parameterisation
via system bus
(C0370)
(configurable in
C0126)
91
External fault
EEr
(TRIP−SET)
a
Communication
ErP0
abort between
...
keypad and
standard device
ErP19
a
EDK82EV113 DE/EN/FR 11.0
Troubleshooting and fault elimination
Cause
Controller has received too many
faulty telegrams via the system
bus and has been disconnected
from the bus
For remote parameterisation via
the system bus (C0370):
Slave does not respond.
Communication monitoring time
has been exceeded
For operation with application
I/O:
Parameter set change−over has
been parameterised incorrectly
For operation with module on
FIF:
Internal error
CAN controller reports "Warning"
or "BUS−OFF" status
Node does not respond or is not
available
For operation with application
I/O:
Parameter set change−over has
been parameterised incorrectly
A digital signal assigned to the
TRIP−Set function is activated
Various
l
Fault elimination
Fault messages
Remedy
l
Check bus termination
l
Check shield connection of the
cables
l
Check PE connection
l
Check bus load, reduce the baud
rate, if necessary
l
Check wiring of the system bus
l
Check system bus configuration
The "parameter set change−over"
signal (C0410/13, C0410/14) must be
connected to the same source in all
parameter sets
Contact Lenze
l
Check bus termination
l
Check shield connection of the
cables
l
Check PE connection
l
Check bus load, reduce the baud
rate, if necessary
l
Check bus termination
l
Check shield connection of the
cables
l
Check PE connection
l
Check bus load, reduce the baud
rate, if necessary
The "parameter set change−over"
signal (C0410/13, C0410/14) must be
connected to the same source in all
paramerter sets
Check external encoder
Contact Lenze
8
159