R4 To 37 Kw Fixed Speed Modbus Table - Ingersoll Rand R30 Information De Produit

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

93014.15.06
EN

R4 to 37 kW Fixed Speed Modbus Table

Register
(40XXX)
1
Status/Control
3
Package Discharge Pressure
4
Sump Pressure
7
Airend Discharge Temperature
8
After-cooler Discharge Temperature
10
Separator Pressure Drop
16
After-cooler Discharge Pressure
65
Running Hours MSB
66
Running Hours LSB
67
Loaded Hours MSB
68
Loaded Hours LSB
98
Rated Pressure
100
Starter Type
101
Modulation Enabled
102
Service Level
103
Service Time Period
104
Dryer Installed
112
Offl ine Pressure
113
Online Pressure
114
Mode of Operation
115
Starter Time (seconds)
116
Auto Restart Time (seconds)
117
Auto Restart ON/OFF
118
Communication Control ON/OFF
119
Remote Start/Stop Enable
121
Power Out Restart Option (PORO) Enable
122
PORO Time (seconds)
123
Auto Start/Stop Delay Time (seconds)
124
Low Ambient Temperature
125
Unloaded Stop Time
128
Lead/Lag
129
Lag Off set
131
Lead/Lag Cycle Length (Hours)
132
Scheduled Start (Day)
133
Scheduled Start (Hour)
134
Scheduled Start (Minute)
135
Scheduled Stop (Day)
136
Scheduled Stop (Hour)
137
Scheduled Stop (Minute)
255
Warning Code
256
Trip Code
400
Reset Web Logins
EN-56
Table 32: R4 To 37 kW Fixed Speed Modbus Table
Variable
Read/Write
Range
R/W
R
R
R
R
R
R
R
R
R
R
R
R
1-3
R
R
0 - 2
R
1000 - 8000
R
R/W
75 - (rated+10)
R/W
65-(offl ine-10)
R/W
0 – 2
R/W
5 – 30
R/W
120 – 3600
R
R
R
R
R/W
10 - 600
R/W
0 - 60
R/W
30 - 60
R/W
10 - 30
R/W
R/W
0 - 45
R/W
0 – 750
R/W
0 - 9
R/W
0 – 23
R/W
0 – 59
R/W
0 - 9
R/W
0 – 23
R/W
0 – 59
R
R
R/W
0-1
Notes
See FIGURE 129
Low Ambient units only
Dryer units only
See Figure 130
0=Disabled
0=Level 0, 1=Level 1, 2=Level 2
Increments of 1000
0=OFF
rated = rated pressure
offl ine = offl ine pressure
See Figure 130
0=OFF
0=OFF
0=OFF
0=OFF
Degree F
0=Lag
psi
See Figure 130
See Figure 130
See Figure 131
See Figure 131
Writing a 1 value will reset the web logins to
factory defaults. After the reset is performed
this value shall be set back to 0
80447162 Rev B

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

R37R45R55R75R90R110 ... Afficher tout

Table des Matières