Hour Meters indicate the hours that: the controller has been powered up,
and the compressor has been running.
Starts indicate the number of times a start is attempted on the
compressor.
Date & Time is adjustable and confi gurable in the GENERAL SETTINGS
folder.
All information on this page is read only.
Pages 3-5: Analog Inputs & Compressor Information
Figure 39 : Analog Inputs & Compressor Information
All information on these pages is read only.
The following analog inputs are displayed in this section:
Package Discharge Pressure
Sump Pressure
Airend Discharge Temperature
Injected Coolant Temperature
After-cooler Discharge Temperature
Separator Pressure Drop
Coolant Filter Pressure Drop
Inlet Vacuum
Remote Pressure (optional)
After-cooler Discharge Pressure (integrated dryer compressors only)
Additionally, the following compressor status readings are included in this
section:
Motor Speed
Package kW
Average Package kW/hour
Average % Capacity
Average Capacity
Energy Cost
Energy Savings
Lifetime Energy Savings
80447162 Rev B
NOTICE
Icon
Meaning
Pressure
Temperature
NOTICE

Operator settings folder

Pages 1-2: Operator Settings
Figure 40 : Operator Settings
The parameters below are adjustable at any time:
Table 18 : Operator Settings
Operator
Default
Settings
Target Pressure
100
Automatic Stop
110
Pressure
Immediate Stop
120
Pressure
% Savings
Modulation
Compared To
Energy Rate
0.000
Reset Averaging
--/--/--
Pages 3-5: Operator Options
Figure 41 : Operator Options
The parameters immediately below are only adjustable when the compressor
is stopped.
The options set points are similar to the operator set points except these set
points cannot be changed while the compressor is running.
Table 19 : Operator Options
Option
Selection Min.
Items
Remote
ON/OFF
---
Sensor
Comm
ON/OFF
---
Control
Min.
Max.
Step
65
145
1
Target+1
Target+10
1
Auto
Auto+10
1
---
---
---
0.000
9999.999
---
-
-
-
Max.
Step
Unit
Installed
option
required?
---
---
---
No
---
---
---
No
EN
Unit
psi
psi
psi
---
---
Date
EN-23