Status Folder - Ingersoll Rand R30 Information De Produit

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

93014.15.06
EN
The master controller MUST be started and running in the sequence.
Otherwise, compressors will revert to their local setpoints.
If the master controller is telling a slave controller to load and the slave's
local pressure is above its maximum offl ine setpoint, or its immediate
stop setpoint, the slave will unload locally, and remain unloaded until
pressure falls below online or target setpoints.
Integral Sequencing – Enabling Integral Sequencing chooses this
compressor to be the sequence Master. The master's package discharge
pressure sensor will be the pressure signal used for the system. The default is
disabled. Please make sure all compressors are set up for integral sequencing
before enabling this function. It is important that only one compressor in
the system have this setpoint enabled, otherwise system behaviour could be
impacted. This setpoint should also only be modifi ed while the compressor is
stopped. Note that the Integral Sequencing master does not have to be the
compressor assigned RS-485 address 1.
Unload Pressure – Determines the pressure at which a compressor will be
unloaded by the system. The system unload pressure should always be set
lower than the local offl ine setpoint of compressors in the system. Note that
when under system control, the compressor will ignore the local pressure
setpoints except for protective functions.
Load Pressure – Determines the pressure at which a compressor will be
loaded by the system. The system unload pressure should always be set
lower than the local offl ine setpoint of compressors in the system. The system
unload pressure should always be set lower than the local offl ine setpoint
of compressors in the system. Note that when under system control, the
compressor will ignore the local pressure setpoints except for protective
functions.
Start Delay Interval – Determines the amount of time between loading
compressors. This prevents all compressors from loading at once. This
setpoint should be set to the longest starting time of any compressor in the
system. In general, this will be equivalent to the star/delta transition time for
a fi xed speed machine, or ramp time for a VSD machine.
Damping – The pressure control "Damping" setting which is used to tune
how quickly the system responds to pressure deviations. The default is 10 and
should not normally be changed.
Tolerance - The pressure control "Tolerance" setting, which is used to tell the
system how to respond to changes in pressure above and below the load/
unload pressures. The default is 3.0 psi and should not normally be changed.
Number of Compressors – Defi nes how many compressors are in the
system. There is a maximum of 4.
Priority – Each compressor can be assigned a priority level. Setting a
priority for a compressor aff ects how the rotation will occur. Compressors
with priority 1 will always be in the lead position(s), followed by priority 2
compressors, and so on. Compressors will only rotate positions with other
compressors of the same priority level.
Sequence – Displays the current load/unload order of the system. Each
compressor in the system is assigned a letter. The letter indicates whether
the machine with the assigned Airbus address is a lead machine (loads fi rst,
unloads last) or one of the trim machines. Letter A is assigned to the lead
machine, B to the next machine to load, C to the third machine to load, and D
to the fi nal machine to load. Machines will unload in the reverse order, such
that A will be the last machine running.
The fi rst position in the - - - - sequence on Integral Sequencing tab, page 3
always refers to the compressor that is assigned Airbus Address 1. The second
position to Airbus Address 2, and so on. Note that the letter sequence may
change due to rotation.
Note that the sequence will only be displayed on the master controller.
Rotate Now – Selecting this setpoint will cause the sequence to shift
according to the priorities, regardless of the rotation interval setpoint.
Rotation Interval – Determines the time period between automatic
sequence rotations.
Time Left – Counts down the time until the sequence rotation will occur.
System Pressure – Shows the current pressure reading that the system is
using for control. This will only be shown on the sequence Master controller.
EN-42

Status folder

All information on these pages is read only.
Some values may only be visible when the factory settings password
is entered.
Page 1 – Analog Inputs
Figure 88 : Analog Inputs
Analog Inputs:
The following analog inputs are displayed in this section.
Package Discharge Pressure – The pressure the compressor is delivering
to the plant
Sump Pressure – The compressor's internal pressure at the sump tank.
Airend Discharge Temperature – The temperature of the air/oil mixture
at the discharge of the compression module.
After-cooler Discharge Temperature – The temperature of the air after
passing through the After-cooler. Note that this will only be shown if the
Low Ambient option has been purchased and installed.
After-cooler Discharge Pressure (integrated dryer units only)
– Pressure the compressor is delivering before the dryer.
Page 2 – Compressor Data
Figure 89 : Compressor data
Compressor Data:
Power ON Hours – The number of hours the controller has been powered
up
Running Hours – The number of hours the compressor's motor has been
running
Loaded Hours - The number of hours the compressor has been
producing air
Real Time Clock - Current time of day
NOTICE
NOTICE
80447162 Rev B

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

R37R45R55R75R90R110 ... Afficher tout

Table des Matières