Fixed Speed Compressor; Home Folder - Ingersoll Rand R30 Information De Produit

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

93014.15.06

Fixed Speed Compressor

Home folder

Page 1: System Overview
This is the factory default display after powering up the system.
Online Pressure Setpoint - indicated in the black box and arrow, which
is always left of center on the gauge. The compressor will load when
package discharge pressure falls below this value.
Offl ine Pressure Setpoint - indicated in the black box and arrow, which
is always right of center on the gauge. The compressor will unload when
package discharge pressure rises above this value.
Package Discharge Pressure - indicated by the large numbers centered
below the gauge and by the black arrow below the gauge. This is the air
pressure that the compressor is supplying to the plant.
Pressure Unit of Measure - indicated below the Package Discharge
Pressure. This is selectable from the GENERAL SETTINGS folder.
Airend Discharge Temperature - indicated by the numbers in the lower
right of the display. This is the temperature of the air/oil mixture at the
discharge of the compression module.
Temperature Unit of Measure - indicated to the right of the Airend
Discharge Temperature. This is selectable from the GENERAL SETTINGS
folder.
Run Hours – indicated by the numbers in the lower left of the display. The
number of hours the compressor motor has been running.
The online and offl ine set points can be selected and modifi ed on this
page. All other information on this page is read only.
Page 2 : Counters
Hour Meters - Indicates the hours that: the controller has been powered
up, the compressor motor has been running, and the compressor has
running loaded.
Starts - Indicates the number of times a start is attempted on the
compressor.
Date & Time – Indicates the current date and time. This is adjustable and
confi gurable in the GENERAL SETTINGS folder.
All information on this page is read only.
80447162 Rev B
Figure 70 : Home Folder
NOTICE
Figure 71 : Counters
NOTICE
Pages 3 & 4 – Analog Inputs and Compressor Information
Figure 72 : Analog Inputs and Compressor Information
Any sensor that is not installed or is reporting a failure will show a [ - - ]
symbol.
All information on this page is read only.
The following analog inputs are displayed in this section.
Package Discharge Pressure – The pressure the compressor is delivering
to the plant.
Sump Pressure – The compressor's internal pressure at the sump tank.
Airend Discharge Temperature – The temperature of the air/oil mixture
at the discharge of the compression module.
After-cooler Discharge Temperature – The temperature of the air after
passing through the after-cooler. Note – Only shown when the Low
Ambient option is purchased and installed.
After-cooler Discharge Pressure – Pressure the compressor is delivering
before the dryer. Note – Only shown when the TAS option is purchased
and installed.
Separator Pressure Drop – The pressure drop across the separator
element.
Dryer Run Status (Integrated dryer units only) – Checkbox that shows
whether the dryer is currently running (checked) or not (blank).
Time and Date
Main Motor Current – Current fl owing through the main motor as
measured by the installed current transducers.
NOTICE
EN
EN-35

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

R37R45R55R75R90R110 ... Afficher tout

Table des Matières