Navigation Keys; Operating Instructions (Xe-50M Controller); Command Keys; Display Layout - Ingersoll Rand R4-11 kW Mode D'emploi

Masquer les pouces Voir aussi pour R4-11 kW:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Figure 62 : Xe-50M

COMMAND KEYS

These keys command the controller to perform actions as specified in the
following table. When any of these keys are pressed the action below will be
initiated and logged in the event log.
Table 16: Xe-50M Command Keys
Icon
Name
Function
Start
Starts the compressor.
Stops the compressor, this button should
Stop
be pressed instead of the E-stop for normal
stopping operation
Navigation Keys Leads the user down or up a navigation path
Clears Warnings and Trips once the condition
Reset
is corrected
Enter
Confirms operation

DISPLAY LAYOUT

Figure 63 : Display Layout
Table 17 : Dislpay Icons
Key
Description
1
Main Display Value
2
Main Display Value Units
3
User Menu Item Display Value
4
User Menu Item Display Units
5
Status Symbols Started, Running, Loaded
6
Service/Fault Symbols Service, Fault: Alarm/Warning/Trip
Started
Running
80448483 Rev.B
RELEASED 16/Dec/2014 10:49:53 GMT

oPERATING INSTRUCTIoNS (XE-50M CoNTRoLLER)

Key
Description
Loaded
Service
Fault: Warning Trip

USER DISPLAY

Table 18: User Display Icons
Main Display Value : Pressure (bar/psi
menu selectable)
Default User Menu item : Temperature
(˚C/˚F menu selectable)
To view alternative user menu items
Press Up or Down
Total Run Hours
Total Run Onload
Hours Until Service Due (countdown
timer based on total run hours)
RS485 Communication Network
Address (*only show if RS485 option
installed)
If a timer event occurs (run-on, stop, blowdown or auto restart
time) the User item display will show the time countdown in seconds. While
a countdown is being displayed normal User items can still be viewed; press
Down.
The display will default back to the User Temperature item after a short
period of no key activity or after a timer events has completed.
If operating in 'Pressure Switch Mode' the main display will show the
detected temperature and the default User Menu item will be total run hours.
Pressure is not displayed in pressure switch mode.
Pressure Switch Mode

STATUS DISPLAY

The operating status is continuously displayed using status symbols.
Table 19 : Status Display Icons
Standby : The compressor is in a started state but
not running. The compressor will automatically
re-start and load when pressure falls to the lower
pressure set point; or a remote load signal.
Running : The compressor is running offload (run-
on-time active)
Loaded : The compressor is running onload
EN
EN-35

Publicité

Table des Matières
loading

Table des Matières