Télécharger Imprimer la page

Ingersoll Rand UP5S 11 Installation, Exploitation Et Maintenance page 5

Publicité

Les langues disponibles

Les langues disponibles

1
KEY
1
Compressor
2
Air Receiver
3
Air Dryer
4
Compressed air filters
5
System demand points
NOTICE
Items [2] to [5] are optional or may be existing items
of plant�� Refer to your Ingersoll Rand distributor /
representative for specific recommendations��
LOCATION IN THE PLANT
The compressor can be installed on any level floor
capable of supporting it�� A dry, well ventilated area where
the atmosphere is clean is recommended�� A minimum of
150 mm (6 inches) should be left at the rear and 1 m
(3 ft) at the sides of the machine for adequate service
access and ventilation��
Adequate clearance needs to be allowed around and
above the machine to permit safe access for specified
maintenance tasks��
Ensure that the machine is positioned securely and on
a stable foundation�� Any risk of movement should be
removed by suitable means, especially to avoid strain on
any rigid discharge piping��
NOTICE
The Main Motor Overload Current set point is preset
into the compressor controller program before
leaving the factory and is not user adjustable�� If this
is required to be changed, due to an input voltage
conversion, contact your local Ingersoll Rand service
provider��
80448418 Rev.C
RELEASED 20/Jul/2016 17:56:55 GMT
All manuals and user guides at all-guides.com
INSTALLATION / HANDLING
Discharge piping should be at least as large as the
discharge connection of the compressor�� All piping
and fittings should be suitably rated for the discharge
pressure��
CAUTION
Screw type compressors [1] should not be installed
in air systems with reciprocating compressors
without means of isolation such as a common
receiver tank�� It is recommended that both types of
compressor be piped to a common receiver using
individual air lines��
CAUTION
The use of plastic bowls on line filters and other
plastic air line components can be hazardous�� Their
safety can be affected by either synthetic coolants
or the additives used in mineral oils�� Ingersoll Rand
recommends that only filters with metal bowls
should be used on any pressurised system��
CAUTION
Before starting machine remove shipping bolt and
discard��
CAUTION
The standard compressor unit is not suitable for
operation in temperatures liable to cause freezing
as condensate water is liable to be produced in the
after cooler and receiver where fitted��
Refer to your Ingersoll Rand distributor for further
information��
DISCHARGE PIPING


Publicité

loading

Ce manuel est également adapté pour:

Up5s 15Up5s 18Up5s 22Up6s 15Up6s 20Up6s 25 ... Afficher tout