Télécharger Imprimer la page

Ingersoll Rand UP5S 11 Installation, Exploitation Et Maintenance page 14

Publicité

Les langues disponibles

Les langues disponibles

OPERATING INSTRUCTIONS (XE-70M CONTROLLER)
EVENTS FOLDER
Pages 1 to a Max of 50
Figure 11: Events folder
The pages in the Events folder document up to the last
250 events that the controller has experienced, with the
time and date of the occurrence�� The events are recorded
in sequence, with number one being the newest and 250
being the oldest�� When a new event occurs, it becomes
number one and all others are shifted up in number��
The page numbers in the Title Bar are used to scroll
through the events, with each page displaying up to five��
Page one displays events one through five, page two
displays six through ten, and so on��
The time and date of the event can be viewed by
navigating to an event and pressing the right arrow
navigation key�� The time and date window can then be
exited by pressing the enter key��
Figure 12 : Events folder
The following items will generate an event��
Power ON
Power OFF
Press the Start Key
Press the Stop Key
Press the Load Key
Press the Unload Key
Starting the compressor remotely
Stopping the compressor remotely
Loading the compressor remotely
Unloading the compressor remotely
Warning
Trip
Start Inhibit
14
RELEASED 20/Jul/2016 17:56:55 GMT
All manuals and user guides at all-guides.com
Active Warnings will show a flashing caution icon
while acknowledged Warnings will a solid icon��
Active Trips will show a flashing trip icon
acknowledged Trips will have a solid icon��
Active Start Inhibits will be listed in the Event log, but
not have an icon present�� The display will indicate the
compressor is not ready to start if a start inhibit is active��
Warning Events List
Sensor Failure ( Not available on this compressor
model)
Xe-70M On-Screen Text: 7ATT Failure
This will occur whenever sensor 7ATT is recognized as
missing or broken�� The sensor failure message shall follow
the following format: 7ATT FAILURE�� The 7ATT sensor
failure will be shown only when the integrated dryer is
installed (accessed in the factory settings menu)�� This
condition must exist for 3 seconds before the warning is
issued��
Change Separator Element
Xe-70M On-Screen Text: Chg Sep Elem
Will occur if the unit is loaded, the package discharge
pressure (4APT) is at least 90 psi and the separator
pressure drop is greater than 12 psi�� This condition must
exist for 3 seconds before the warning is issued��
Note that the Enable 3APT setpoint must be turned ON
for this warning to occur
High Airend Discharge Temperature
Xe-70M On-Screen Text: High A/E Disch T
Will occur if the unit is running and 2ATT is greater than
221 deg F (97% of 228) and the unit is running�� This
condition must exist for 3 seconds before the warning is
issued��
High Sump Pressure
Xe-70M On-Screen Text: High Sump Pres
If the unit is running loaded, has been loaded for at least 8
seconds and the sump pressure is more than 25 psi above
the rated pressure for the compressor�� If this warning
occurs, the online and offline pressures will be reduced��
For example, a rated pressure of 100 psi would have a
maximum offline pressure of 110 psi�� This warning would
occur if the sump pressure goes above 125 psi in this
example�� This condition must exist for 3 seconds before
the warning is issued��
Note that the Enable 3APT setpoint must be turned ON
for this warning to occur��
while
80448418 Rev.C

Publicité

loading

Ce manuel est également adapté pour:

Up5s 15Up5s 18Up5s 22Up6s 15Up6s 20Up6s 25 ... Afficher tout