OPERATING INSTRUCTIONS (XE-70M CONTROLLER)
Page 2 : Counters
Figure 6 : Counters
Hour Meters - Indicates the hours that: the controller
has been powered up, the compressor motor has been
running, and the compressor has running loaded��
Starts - Indicates the number of times a start is
attempted on the compressor��
Date & Time – Indicates the current date and time��
This is adjustable and configurable in the GENERAL
SETTINGS folder��
NOTICE
All information on this page is read only��
Pages 3 & 4 – Analog Inputs and Compressor
Information
Figure 7 : Analog Inputs and Compressor Information
Any sensor that is not installed or is reporting a failure will
show a [ - - ] symbol��
NOTICE
All information on this page is read only��
The following analog inputs are displayed in this section��
Package Discharge Pressure – The pressure the
compressor is delivering to the plant��
Sump Pressure – The compressor's internal pressure at
80448418 Rev.C
RELEASED 20/Jul/2016 17:56:55 GMT
All manuals and user guides at all-guides.com
Pages 1-2: Operator Settings
The below values are all setpoints
Online Pressure – The compressor will load when the
package discharge pressure falls below this value��
Range (in PSI): 65 to Offline Pressure - 10
Offline Pressure – The compressor will unload when
package discharge pressure rises above this value��
Range (in PSI): 75 to Rated Pressure + 10�� Please note that
the range will be reduced by 7 psi when operating a TAS
the sump tank��
Airend Discharge Temperature – The temperature of
the air/oil mixture at the discharge of the compression
module��
After-cooler Discharge Temperature ( Not available
on this compressor model)– The temperature of the
air after passing through the after-cooler�� Note – Only
shown when the Low Ambient option is purchased and
installed��
After-cooler Discharge Pressure ( Not available on
this compressor model)– Pressure the compressor is
delivering before the dryer�� Note – Only shown when
the TAS option is purchased and installed��
Separator Pressure Drop – The pressure drop across
the separator element��
Dryer Run Status (Integrated dryer units only) ( Not
available on this compressor model) – Checkbox that
shows whether the dryer is currently running (checked)
or not (blank)��
Time and Date
Main Motor Current – Current flowing through the
main motor as measured by the installed current
transducers��
OPERATOR SETTINGS FOLDER
Figure 8 : Operator Settings
11