6.5 Temperatures

Room temperature adjustment
Cool T-supply air min.
Maximum room temperature
Room temperature adjustment
Parameter
Room temperature
adjustment
Causes for deviation in actual room
temperature:
● Comfort control unit, external room sensor
or bus room sensor in unfavourable installa-
tion location.
● Exhaust air temperature sensor tolerance
too high.
This parameter can be used to adjust the
actual room temperature. The adjustment re-
lates to the room sensor selected under room
sensor configuration  Chapter 6.2.
Example: Actual room temperature measured
on comfort control unit 20.3 °C. With "Room
temperature adjustment" of -0.4 K, an actual
room temperature of 19.9 °C is displayed.
Cool T-supply air min.
Parameter
Cool T-supply air min. 8 ... 14 ... 29 °C
Limits the minimum supply air temperature
if cooling with bypass (
170
160 Flat 300 Flat
heat exchanger.
Bypass partially closes and/or the brine earth
heat exchanger cuts out when the tempera-
ture falls below the set temperature.
The ventilation unit regulates the supply air
temperature to the set value.
to
170
Trio
and
72
Setting
-3 ... 0 ... +3 K
Setting
310/410 320/470
) or brine earth
Does not apply
.
Maximum room temperature
Parameter
Maximum
room temperature
310/410 320/470 160 Flat 300 Flat
170
The control releases cooling via the bypass
when the set maximum room temperature
is reached (measurement on temperature
sensor).
Conditions for cooling via the bypass
● Summer season or T
with simple control unit in solo mode
and
● T
< T
outside air
room
Trio
The control releases cooling via the brine
EHE when the set maximum room tempera-
ture (measurement on temperature sensor)
is exceeded by 1 K.
Setting
18 ... 26 ... 30 °C
> 5 °C
outside air