Filter service life, external filter
Filter change, external filter
Room filter
Filter service life, room filter
Filter change, room filter
Duration of ventilation level
Supply and exhaust air valves are set
i
during initial commissioning. Open or
close them to set the values specified
by the planning office.
Volumetric flow measurement (nominal
ventilation)
Parameter
Volumetric flow
measurement
(nominal ventilation)
After activating the volumetric flow measure-
ment, the fans are run for a maximum of
3 hours in nominal ventilation.
This allows the supply and exhaust air volu-
metric flows in the building to be calibrated
without the air volumes being changed by
sensor values. The function switches off
automatically after 3 hours.
If deactivate is selected or the installer level is
exited, this function switches off immediately.
Volumetric flow of ventilation level
Reduced ventilation „RV" (in m³/h)
Type
WR 310 / WS 320 ..
WR 410 / WS 470 ..
WS 170
WS 160 Flat
WS 300 Flat
Trio
Nominal ventilation „NV" (in m³/h)
Setting
activate
deactivate
min.
ex
max.
works
80
120
320
80
160
490
40
60
160
40
60
160
80
100
300
40
60
120
6 Settings main menu | UK
Type
WR 310 / WS 320 ..
WR 410 / WS 470 ..
WS 170
WS 160 Flat
WS 300 Flat
Trio
Intensive ventilation „IV" (in m³/h)
Type
WR 310 / WS 320 ..
WR 410 / WS 470 ..
WS 170
WS 160 Flat
WS 300 Flat
Trio
The setpoint volumetric flow setting applies to
both fans. With humidity protection ventilation,
the fans run in interval mode
13 min. RV – 17 min. Off – 13 min RV etc.
We recommend setting the volumetric flow for
NV first.
The RV and IV volumetric flows are set auto-
matically by the control on the basis of the
NV reference value 1/3 less than (RV) and 1/3
greater than (IV).
310/410 320/470
Example
NV 150 m³/h  RV 100 m³/h, IL 200 m³/h.
170
Example
NV 90 m³/h  RV 60 m³/h, IL 120 m³/h.
The IV and RV volumetric flows can also be
set manually. Condition:
Volumetric flow Intensive ventilation > Nomi-
nal ventilation > Reduced ventilation.
EA SA (Exhaust air/supply air) adjustment
Parameter
EA SA adjustment
RV ventilation level
EA SA adjustment
NV ventilation level
min.
ex
max.
works
80
180
320
80
240
490
40
90
160
40
90
160
80
150
300
40
90
120
min.
ex
max.
works
80
240
320
80
320
490
40
120
160
40
120
160
80
200
300
40
120
120
Flat
Trio
Setting
min. -50 m³/h
max. +50 m³/h
min. -50 m³/h
max. +50 m³/h
69