Comfort control unit (touchscreen control
unit)
Parameter
Comfort control unit
When commissioning with comfort
i
control unit briefly connected
1. Connect comfort control unit to the con-
trolled domestic ventilation control (circuit
board A2) in accordance with installation
instructions and switch on.
2. Select this parameter and activate the
interface with "yes".
3. When commissioning is complete, deacti-
vate the interface with "no", otherwise
operation is undefined.
4. Lastly, remove the connection to the con-
trolled domestic ventilation control.
ModBus
Setting
only possible with commissioning
i
software or web server.
Parameter
ModBus
Simple control unit
Solo mode only
i
control unit is connected. Function not
available with
tool.
Parameter
Simple control unit
Solo: Ventilation unit is operated with simple
control unit supplied + maximum of 4 optional
Setting
no: Interface for
comfort control unit
deactivated
yes: Interface for
comfort control unit
activated
Setting
no / yes:
For detailed info
 download area at
www.maico-ventila-
toren.com.
possible if no comfort
app or
web
Setting
Solo
Auxiliary
Inactive
Digital
6 Settings main menu | UK
simple control units.
Auxiliary: Ventilation unit is operated with one
optional comfort control unit + maximum of
5 optional simple control units.
Inactive: The connections are needed for
extra sensors (sensor 3 and 4). Function only
if no simple control unit is connected.
Digital: A 3-stage simple GLT circuit (e.g.
KNX) can be created via an actuator for
ventilation level adjustment  wiring diagram
in installation instructions, Chapter 19.
Simple control unit blocking Off
Parameter
Simple control unit
blocking
ventilation level Off
* If the switch-off function is disabled, the
ventilation unit runs with at least interval ven-
tilation (ventilation for humidity protection).
Switching contact function
310/410
320/470
300 Flat
Trio
ATTENTION with pre-heating/supple-
mentary heating
Incorrect installation will result in unit
damage. If external pre-heating or sup-
plementary heating is selected, the power
supply for the component should be switched
via an external relay.
Setting
yes: Ventilation unit's
switch-off function with
simple control unit
disabled *
no: Ventilation unit's
switch-off function
with simple control
unit activated
160 Flat