Ventilation - Maico WR 310 Notice De Mise En Service Et D'entretien

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

UK | 6 Settings main menu
Parameter
Switching contact
One of the aforementioned external compo-
nents can be switched with the potential-free
switching contact (max. 5 A) of the basic
circuit board (main circuit board).
Additional settings for supplementary
heating switching points
310/410
320/470
300 Flat
Trio
1. Under Switching contact select the
Supplementary heating parameter.
2. Under supplementary heating ( Chap. 6.11)
set the Supplementary heating parame-
ter to "yes".
Adjust switching point to Hysteresis
setpoint temperature.
Set Supplementary heating parameter
to "no".
For additional information  Chapter 6.11.
Additional settings for brine earth heat
exchanger switching points
310/410
320/470
300 Flat
Trio
1. Under Switching contact, select the
Brine earth heat exchanger parameter.
2. Under brine earth heat exchanger (
Chapter 6.8)
set the Brine earth heat exchanger
parameter to "yes".
Adjust switching points to T-air inlet
offset heating, T-air inlet hysteresis heating
and T-air inlet hysteresis cooling para-
meters.
Set Brine earth heat exchanger para-
meter to "no". For additional information
68
Setting
Alarm
Filter change
Operating display
Supplementary
heating
Pre-heating
External shutter
Brine EHE (uncon-
trolled pump)
Cooling function
160 Flat
160 Flat
 Chapter 9.1.
Bypass
310/410
320/470
160 Flat
300 Flat
Parameter
Bypass
If retrofitting, activate bypass with "yes".
PTC heat register
310/410
320/470
160 Flat
300 Flat
Parameter
PTC heat register
If retrofitting, activate PTC heat register with "yes".
Heat exchanger type
310/410
320/470
Parameter
Heat exchanger type Sensitive / enthalpy:
If retrofitting, activate suitable heat exchanger type.

6.3 Ventilation

Volumetric flow measurement (nominal
ventilation)
Volumetric flow of ventilation level:
Reduced ventilation
Nominal ventilation
Intensive ventilation
EA SA (Exhaust air/supply air) adjustment:
EA SA adjustment, reduced ventilation
EA SA adjustment, nominal ventilation
EA SA adjustment, intensive ventilation
Filter service life, unit filter
Filter change, unit filter
External filter
170
Setting
yes / no: depending
on unit equipment
170
Trio
Setting
yes / no: depending
on unit equipment
170
Setting
depending on unit
equipment