Connecting The Network Cable (Ac Cable) - Bosch BPT-S 3 Manuel De Service

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

English
NOTICE
Bosch Power Tec GmbH
5.1.3

Connecting the network cable (AC cable)

Materials required
Cable stripper
Suitable 4 mm slotted screwdriver
30 mm spanner
Mains plug (included in delivery)
– For wire cross-section 2.5 to 6 mm
flexible (with wire end ferrule without plastic
collar)
– 3 different cable thicknesses for external cable
diameters 8 to 12 mm, 12 to 16 mm, 16 to 21 mm
Permitted connectors: Only connect the integrated
AC connection of the string inverter with the AC plug
included in the delivery. If you lose the original AC
plug: Contact Bosch Power Tec Service (see contact
details on the back of the manual).
Minimum permitted bending radii: At least 4 x cable
diameter
Material damage due to incorrect DC connection
and AC connection
If the DC cables and AC cables are bent beyond the
minimum permitted bending radii, the cables may
break and both the plug/socket and the seal may be
damaged.
Observe the minimum bending radii of the DC cable
and AC cable
Absorb mechanical loads before they reach the
plug/socket (e.g. using cable ties)
Bosch BPT-S 3 / 3.68 / 4 / 4.6 | Operating manual
Installation | 65
2
, rigid or

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Bpt-s 4.6

Table des Matières