External Off Function; Volumetric Flow Adjustment For Additional Exhaust Fans (Er/Eca Units); Radio-Controlled Operation (Enocean) - Maico PP 45 O Notice D'utilisation

Système de ventilation pushpull
Masquer les pouces Voir aussi pour PP 45 O:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

UK | 7 Radio-controlled operation (EnOcean)
The intermittent ventilation is not
i
available for ventilation units
connected to the power units.
If any key on the control is pressed during
intermittent ventilation, the ventilation units
switch back to the ventilation level used
previously.

6.10 External OFF function

RLS 45 O DS 45 RC
RLS 45 K
: Function available.
The external OFF function is switched
i
using an optional, central on/off
switch connected to the control's
230 V input. The switch must
be configured for the external
OFF function when in service mode,
parameter 230 V AC input
 Installation instructions.
This function can be used to switch off all the
ventilation system's ventilation units.
6.11 Volumetric flow adjustment for
additional exhaust fans (ER/ECA units)
RLS 45 O
: Function not available.
RLS 45 K
: Function available.
This function is switched
i
using an optional, central on/off
switch connected to the control's
230 V input. The switch must
be released for the supply air operation
function when in service mode,
parameter 230 V AC input
 Installation instructions.
This function can be used to undertake a vol-
umetric flow adjustment with exhaust air units,
for example with Maico exhaust fans ER 60
or ECA 100 ipro.
When the function is activated, all ventilation
units connected to the room air control adopt
the volumetric flow compensation – note
setting of connected units!
A certain ventilation level is specified for the
registered unit pairs – this depends on the
number of units.
30
: Function not available.
Compensation of volumetric flow is only ever
undertaken by the ventilation units connected
to the room air control affected. The volumet-
ric flow compensation function is not taken
into account by other power units and room
air controls in the ventilation system.
The same applies to the special intermittent
ventilation and sleep mode functions.
When intermittent ventilation/sleep mode is
activated, the supply air operation function
takes priority. The timer time for the intermit-
tent ventilation/sleep function continues to run
in the background.
If the exhaust air units integrated into the
ventilation system have an overrun timer,
the duration of the overrun time must be
selected in the room air control.
The overrun time can be adjusted in service
mode (0, 6 or 15 minutes). The overrun time
cannot be interrupted by pressing keys.
7 Radio-controlled operation
(EnOcean)
Radio-controlled operation of PP 45 venti-
lation units is realised using EnOcean radio
components.
Purely radio-
PP 45 combi system
controlled
with wired and radio-con-
PP45 system
trolled components
DS 45 RC
+
PP 45 RC
PP 45 RC
...
● PP 45 EO extension module can only be
combined with PP 45 RC unit pairs. Other-
wise, wired operation is required.
● For range of radio components
 Chapter 12, Technical data.
● Radio mode (Maico Smart/EnOcean) is
activated by the specialist installer. Once
radio operation has been activated, you can
teach in/delete EnOcean radio components
directly on the ventilation unit.
RLS 45 K
PP 45 EO
+
+
max. 6
PP 45 RC
PP 45 K
PP 45 O

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Pp 45 kPp 45 rcRls 45 oRls 45 kDs 45 rc0095.0241

Table des Matières