Wiring Of The System Bus (Can) - Lenze 9300 vector Série Instructions De Montage

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

5.9

Wiring of the system bus (CAN)

Installation material required from the scope of supply:
Description
Terminal strip, 3−pole
Wiring
A
1
93XX
X4
HI
LO
120
Fig. 5−30
(
Stop!
Connect a 120 W terminating resistor to the first and last bus device.
We recommend the use of CAN cables in accordance with ISO 11898−2:
CAN cable in accordance with ISO 11898−2
Cable type
Impedance
Cable resistance/cross−section
Signal propagation delay
EDKVF9333V DE/EN/FR 7.2
A
2
93XX
GND
PE
X4
HI
LO
GND
PE
System bus (CAN) wiring
A
Bus device 1 (controller)
1
A
Bus device 2 (controller)
2
A
Bus device 3 (controller)
3
A
Bus device n (e. g. PLC), n = max. 63
n
X4/GND
CAN−GND: System bus reference potential
X4/LO
CAN−LOW: System bus LOW (data line)
X4/HI
CAN−HIGH: System bus HIGH (data line)
Cable length £ 300 m £ 70 mW/m / 0.25 … 0.34 mm
Cable length 301 … 1000 m £ 40 mW/m / 0.5 mm
l
Electrical installation
Wiring of the system bus (CAN)
Use
Connection of system bus (CAN) at X4
A
A
3
93XX
X4
HI
LO
GND
PE
Paired with shielding
120 W (95 ... 140 W)
£ 5 ns/m
Quantity
1
n
HI
LO
GND
PE
120
9300VEC054
2
(AWG22)
2
(AWG20)
5
211

Publicité

Table des Matières
loading

Table des Matières