Installation according to EMC (installation of a CE−typical drive system)
Control cables
For lengths of 200 mm and more, use only shielded cables for analog and digital
ƒ
inputs and outputs. Under 200 mm, unshielded but twisted cables may be used.
Connect the shield correctly:
ƒ
– The shield connections of the control cables must be at a distance of at least
50 mm from the shield connections of the motor cables and DC cables.
– For cables for digital inputs and outputs, connect the shield at both ends.
– For cables for analog inputs and outputs, only connect the shield at the drive
controller end.