Electrical installation
Standard devices in the power range 0.37 ... 11 kW
Motor connection
U, V, W
0.5...0.6 Nm
T1, T2
4.4...5.3 lb-in
Fig. 5−6
176

2
3
PE
U, V, W
T1
T2
T1, T2
U
V
W
1
0
Motor connection with PTC thermistor or thermal contact (NC contact)
 0
Motor connection with Lenze system cable with integrated control cable for the motor
temperature monitoring
1
Shield sheet
Clamp entire shield and shield of the control cable for the motor temperature monitoring
with the straps. If required, fix by means of cable tie.
‚ 0
Motor cable connection and separate control cable for the motor temperature monitoring
1
Shield sheet
Clamp shield of the motor cable and shield of the cable for the motor temperature
monitoring with the straps. If required, fix by means of cable tie.
2
U, V, W
Motor cable connection
Check the correct polarity. Observe maximum length of the motor cable. Use wire end ferrules
for flexible cables.
Max. connectable cable cross−section: 4 mm
3
T1, T2 for motor temperature monitoring
Cable connection for PTC thermistors or thermal contacts (NC contacts)
l
2
3
PE
T1
T2
0.5...0.6 Nm
4.4...5.3 lb-in
U
V
W
1
0
2
, with pin−end connector > 4 mm
9300std011
2
EDKVF9333V DE/EN/FR 7.2