OUTPUT POWER OFF

OUTPUT POWER OFF
OUTPUT POWER OFF
OUTPUT POWER OFF
OUTPUT POWER OFF
These products allow to turn OFF, manually, the
output signal in order to stop the control.
To turn OFF the output signal, push continuously
the
pushbutton first and then push FN
pushbutton.
Maintaining pressure on both of them for more
than 3 seconds, the instrument will show "OFF"
instead of the set point value.
For LDS model, since it has only one display, it is
possible to toggle from "OFF" to measured value
by depressing the
pushbutton (the LEDs of the
bargraph will be flashing to show that the
instrument is working as an indicator only).
In the output power off condition the alarms are in no
alarm condition (the alarm output status depends by
the type of alarm action programmed) and the
parameters can be re-viewed and modified.
When it is desired to come back to the normal
control, push continuously the
pushbutton first
and then push the FN pushbuttons.
Maintaining the pressures on both of them for
more than 3 seconds, the instrument returns in
NORMAL DISPLAY MODE.
NOTES
NOTES
NOTES :
NOTES
NOTES
1) If the output is turned OFF when the SMART
function was performing the first part of the
algorithm (LED ST is flashing), the SMART
function will be aborted and when the
instrument comes back to the normal control,
the SMART function will be disabled.
If the output is turned OFF when the SMART
function was performing the second part of the
algorithm (LED ST is lighting), the SMART
function will be stopped and, when the
instrument comes back to the normal control,
the smart function also will be activated.
2) If the instrument is turned OFF with the output
power off function enabled, at the next start up
lxs-1-0f.pmd
12
the instrument will automatically enabled again
this function.

DIRECT ACCESS TO THE SET POINT

DIRECT ACCESS TO THE SET POINT
DIRECT ACCESS TO THE SET POINT
DIRECT ACCESS TO THE SET POINT
DIRECT ACCESS TO THE SET POINT
MODIFICATION
MODIFICATION
MODIFICATION
MODIFICATION
MODIFICATION
The instrument allows to modified the set point
value without to use the FN pushbutton.
When a direct access to set point modification is
required, proceed as follow:
1)
Push, for more than 3 seconds, the
pushbutton; the set point value, will be
displayed and it will start to change.
2)
Using the
and
pushbuttons, it is
possible to set the desired value.
3)
When the desired value is reached, do not
push any pushbutton for more than 3 second,
the new set point will become operative after
3 second from the last pushbutton pressure.
If, during this procedure, there is no interest in
memorizing the new value, push the FN
pushbutton; the instrument returns automatically
to the normal display mode without having
memorized the new set point.
DISPLAY OF THE SET POINT VALUE
DISPLAY OF THE SET POINT VALUE
DISPLAY OF THE SET POINT VALUE
DISPLAY OF THE SET POINT VALUE
DISPLAY OF THE SET POINT VALUE
(LDS only)
(LDS only)
(LDS only)
(LDS only)
(LDS only)
To display the programmed set point value push
the
pushbutton.
The display will show the set point value and the
decimal point of the last significant digit will flash
to indicate that the number shown is the set point
value.
To come back to display the measured value,
push the
pushbutton again.
GB