Connections are to be made with the instrument
housing installed in its proper location.
Fig. 2 REAR TERMINAL BLOCK
lxs-1-0f.pmd
2
A) MEASURING INPUTS
A) MEASURING INPUTS
A) MEASURING INPUTS
A) MEASURING INPUTS
A) MEASURING INPUTS
NOTE
NOTE
NOTE: Any external components (like zener
NOTE
NOTE
barriers etc.) connected between sensor and
input terminals may cause errors in measurement
due to excessive and/or not balanced line
resistance or possible leakage currents.
TC INPUT
TC INPUT
TC INPUT
TC INPUT
TC INPUT
3
+
_
2
3
+
_
2
Fig. 4 THERMOCOUPLE INPUT WIRING
NOTE
NOTE
NOTE:
NOTE
NOTE
1) Don't run input wires together with power
cables.
2) For TC wiring use proper compensating cable
preferable shielded.
3) when a shielded cable is used, it should be
connected at one point only.
GB
GB
GB
GB
GB
2
16/01/2004, 9.29
Shield
Shield