N O T E :
N O T E : when an overrange or an underrange is
N O T E :
N O T E :
N O T E :
detected, the alarm operate as in
presence of the maximum or the
minimum measurable value respectively.
To eliminate the OUT OF RANGE condition,
proceed as follows:
1) Check the input signal source and the
connecting line.
2) Make sure that the input signal is in
accordance with instrument configuration.
Otherwise, modify the input configuration (see
chapter 3.2).
3) If no error is detected, send back the
instrument to your supplier for a check.
ERRORS
ERRORS
ERRORS
ERRORS
ERRORS
Diagnostics are made at instrument switch-on
and during normal mode of operation.
If a fault condition (error) is detected, the lower
display will show the message "Er" while the
upper display shows the relative error code.
For LDS model, the display will show alternatly
"Er" and the error number.
The following is a list of possible errors in
numerical order.
Also causes, instrument output conditions and
possible remedies are briefly described.
Some errors reset the instrument; if the error
persist, send back the instrument to your supplier.
lxs-1-0f.pmd
16

ERROR LIST

ERROR LIST
ERROR LIST
ERROR LIST
ERROR LIST
100
Write EEPROM error.
150
General hardware error on the CPU
card.
200
Tentative to write on protected
memory.
201 - 2xx
Configuration parameter error. The
two less significant digit's shown the
number of the wrong parameter (ex.
209 Err show an Error on P9
parameter)
301
RTD calibration error.
305
Thermocouple input calibration
error.
307
RJ input calibration error
400
Control parameters error
500
Auto-zero error
502
RJ error
510
Error during calibration procedure
NOTE
NOTE
NOTE
NOTE
NOTE
1) When a configuration parameter error is
detected, it is sufficient to repeat the configura-
tion procedure of the specify parameter.
2) If an error 400 is detected, push contemporar-
ily the
and
pushbuttons for loading the
default parameters then repeat control
parameter setting.
3) For all the other errors, contact your supplier.