Télécharger Imprimer la page

Lenze EMZ9371BC Instructions De Mise En Service page 111

Publicité

Les langues disponibles

Les langues disponibles

Step
1.
Connect the keypad to
standard device 1
2.
Inhibit controller
3.
Select C0003 in the
"Load/Store" menu
4.
Change to the parameter level
5.
Copy all parameter set into the
keypad
6.
Start copying
7.
Change to the code level
8.
Enable controller
9.
Remove keypad from standard
device 1
Copying parameter sets fom keypad into the standard device
Step
1.
Connect the keypad to
standard device 2
2.
Inhibit controller
3.
Pull the plugs X5 and X6
4.
Select C0002 in the
"Load/Store" menu
5.
Change to the parameter level
EDK9371BC DE/EN/FR 3.1
Parameterisation 9300 series
Key sequence
z y Z Y
V
z
T V
V
A
V
B
Key sequence
z y Z Y
V
l
Transmit parameter sets
Action
Terminal X5/28 = LOW
The drive coasts.
Select code C0003 "PAR SAVE" in the
"Load/Store" menu using the arrow keys.
Display "0" and "READY"
The settings saved in the keypad are
overwritten.
Set "11" "Save extern"
The "RDY" status display goes off. As
parameter value "BUSY" is displayed.
If "BUSY" goes off after approx. one
minute, all parameter sets were copied
into the keypad. The "RDY" status display
is lit.
Display of the operating level
Display C0003 and "PAR SAVE"
Terminal X5/28 = HIGH
Action
Terminal X5/28 = LOW
The "IMP" status display is it.
The drive coasts
All control terminals have the defined
"LOW" status.
Select code C0002 "PAR LOAD" in the
"Load/Store" menu using the arrow keys.
The active parameter set is shown, e. g.
display "0" and "Load Default"
8
111

Publicité

loading

Ce manuel est également adapté pour:

E82zbbxcEdk9371bc