Télécharger Imprimer la page

Lenze EMZ9371BC Instructions De Mise En Service page 84

Publicité

Les langues disponibles

Les langues disponibles

7
Parameterisation 8200 vector/8200 motec
Restoring default (as delivered) settings
Step
l
Load parameter sets (PARx and FPAR1):
– Restore the delivery
status in the selected
parameter set of the
standard device and the
fieldbus function
module
7.
Start copying
8.
Change to the code level
9.
Enable the controller
84
Key sequence
z
T V
V
A
V
B
U
l
Action
Load PAR1 and FPAR1
ð
Set "61" "Key−>FP1&PAR1"
Load PAR2 and FPAR1
ð
Set "62" "Key−>FP1&PAR2"
Load PAR3 and FPAR1
ð
Set "63" "Key−>FP1&PAR3"
Load PAR4 and FPAR1
ð
Set "64" "Key−>FP1&PAR4"
The selected parameter sets are loaded
into the standard device or into the
function module.
"LOADING..." is displayed.
If "LOADING..." goes out, the loading
process has been completed.
The operating level is displayed
"Param managm" is displayed in C0002
The drive restarts
EDK9371BC DE/EN/FR 3.1

Publicité

loading

Ce manuel est également adapté pour:

E82zbbxcEdk9371bc