Remote parameterisation of system bus devices
If controllers are networked via system bus (CAN) it is possible to remotely parameterise all
other system bus participants from one central place of the network.
For this purpose use the menu "Remote para":
Step
1.
Select menu 3 "Remote para"
2.
Change to the code level
3.
Change to parameter level
4.
Set the node address of the
system bus participant you
want to parameterise
5.
Change to the code level
6.
Set parameters
7.
Parameterise remotely other
system bus participants, if
necessary
Do not forget to switch off the remote parameter setting after having completed the settings:
8.
Select menu 3 "Remote para"
9.
Change to the code level
10.
Change to parameter level
11.
Switch off the remote
parameter setting
The remote parameter setting is completed
EDK9371BC DE/EN/FR 3.1
Parameterisation 8200 vector/8200 motec
Remote parameterisation of system bus devices
Keys
z y Z Y
Z
V
z
A
T V
B
V
A
V
B
z y Z Y
Z
V
y
l
Action
Change to the menu "Remote para" with
the arrow keys
Display of code C0370 "CANremot para"
Display of the current parameter value:
"0" = OFF
Select node address
Display of "Nodexx"
Confirm node address
Display of operation level
Display of C0370 "CANremot para"
All settings are directed to the selected
system bus participant
Restart "loop" at step 1.
Change to the menu "Remote para" with
the arrow keys
Display of code C0370 "CANremot para"
Display of the node address "Nodexx"
activated last
Set "0" = OFF