Télécharger Imprimer la page

Chloride Power Protection Linear Plus Manuel D'utilisation page 8

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 73
Safety
Leakage currents
Danger
Connect the protection earth (PE) safety conductor before any other
cables are connected.
Radio interference
The Linear Plus is a Radio Interference Class A product, Linear Plus RM is a
class B product
The UPS device may cause radio interference. Do not place it near devices
which are especially susceptible to electromagnetical interference (e.g.
transmitters/receivers, radar, metal detectors, anti-theft devices).
Batteries
Battery maintenance must be carried out by authorised personnel.
• The batteries installed in the UPS and within the battery extensions
may contain electrolyte. Under normal conditions the containers are
dry. A damaged battery may leak electrolyte which can be dangerous in
contact with the skin and cause irritation to the eyes. Should this
happen wash the affected part with copious amounts of water and
seek immediate medical advice.
• Voltage is always present on the battery contacts.
• Even when discharged a battery has the capacity to supply a high short
circuit current, which, in addition to causing damage to the battery itself
and to associated cables, may expose the operator to the risk of burns.
• The voltage of a single cell of a single battery block is not dangerous.
However a number of cells or battery blocks, connected in series, can
produce hazardous voltages.
• The accumulator is a "hermetic" type battery and must not be kept in
storage or disuse for periods exceeding 6 months at 20°C without
being recharged (having been charged to 100% at the beginning of any
such period). If this period is exceeded it is essential that the batteries
be recharged, which requires that the UPS be switched on. If these
conditions are not respected the performance of the battery can no
longer be guaranteed. We advise recharging the batteries at least once
every 4 months.
EN-6
User Handbook
CHLORIDE LINEAR Plus/RM
SU59802UM01, rev.3/ Last modified: 08/2005

Publicité

loading

Ce manuel est également adapté pour:

Linear plus rm