CHLORIDE LINEAR Plus/RM
load
Table 14: Backup time according to load indication (standard devices with batteries integrated)
The current battery capacity can be read from the LED chain BATTERY (see
table below).
.
Table 15: Battery capacity according to LED chain "battery"
The most reliable method, however, is the application of our UPS software.
With this software, the projected remaining battery capacity is permanently
indicated both before and during a mains failures. Furthermore, shutdown
procedures can be automated. Depending on the application program,
operating system and computer hardware, it can be ensured that in the
event of a mains failure the application programs are automatically closed,
the subscribers logged in at the server are logged out, the data are stored
and the operating systems are shut down. For further information please
refer to our publication about the CHLORIDE connectivity solutions.
Once the mains voltage returns, the UPS automatically initiates a restart.
The connected computer systems are booted and their operating systems
are started. Depending on the installed software, the computer's status
before the mains failure can be re-established exactly.
In the event of overload or internal failure, the load is transferred to the
mains via an automatic bypass, without interruption. As soon as normal
conditions are re-established, the unit switches automatically to the
inverter.
Operating modes Linear Plus RM
The UPS has three different operating modes when it is switched on.
User Handbook SU59802UM01, rev.3/ Last modified: 08/2005
load in %
RM 6kVA/10kVA
95-105
6 min /5 min
75-95
9 min
55-75
17 min
30-55
31 min
1-30
60 min
Battery capacity in %
1-35
35-55
55-75
75-95
95-100
Operating the Device
EN-45