Installation
Installation
Electrical preparations
It must be ensured that the live input source cannot accidentally be
connected to the UPS during installation.
Danger
Installation may be carried out only by qualified technicians and in
conformity with the applicable safety standards.
Danger:
Electrical shock hazard: Even when the unit is disconnected from the
mains, hazardous voltage may still be supplied by the battery. Both
poles should, therefore, be disconnected before carrying out
maintenance work inside the UPS.
For electrical installation, the nominal current rating of the source must be
observed. The UPS is not suitable for connection to 16A sub-distribution
systems.
Installation data
Ambient temperature
Relative humidity (w/o condensing at 20°C)
Max. altitude (w/o derating)
Cable inlet
Air inlet
Air outlet
Table 3: Environment data
EN-16
0 °C to +40 °C
90 %
1000 m a.s.l.
bottom at the rear side
sides (Tower UPS) / front (RM UPS)
rear (Tower UPS and RM UPS)
User Handbook
CHLORIDE LINEAR Plus/RM
SU59802UM01, rev.3/ Last modified: 08/2005