Télécharger Imprimer la page

Chloride Power Protection Linear Plus Manuel D'utilisation page 15

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 73
CHLORIDE LINEAR Plus/RM
Environmental conditions
The UPS Linear Plus must be installed vertically, the UPS Linear PlusRM
horizontally, on a level and even surface and in an area protected from
extremes of temperature, water and humidity and the presence of
conductive powder or dust. (See Table 3 on page EN-16). Do not stack units
and do not place any objects on top of a unit.
The functional temperature range of the UPS is 0 °C to 40 °C.
The ideal ambient temperature range is 15 °C to 25 °C.
The battery life is defined at 20 °C. Each increment of 10 °C above 25 °C
reduces the expected life by 50%.
Access to area
The area must have sufficient space for the installation operation to be
carried out. Access doors must be sufficiently large to permit passage of the
unit (See "Installation" on page EN-16).
Floor loading
Taking into consideration the weight of the UPS as reported in Table 4 on
page EN-17, it is necessary that the floor in the chosen location be capable
of supporting the weight of the unit.
Rack loading
Taking into consideration the weight of the RM UPS/batteries as reported in
Table 6 on page EN-19, it is necessary that the chosen cabinet be capable
of supporting the weight of the unit / batteries.
Inventory list
• Parallelable UPS types are equipped with
- 1 control cable, 25-pin
- 1 jumper for terminals S1-S2
User Handbook SU59802UM01, rev.3/ Last modified: 08/2005