Operating the Device
Buzzer alarm operation
Window 33. The buzzer alarm can be switched ON or OFF.
Clear fault
Window 32. Present fault condition can be reset if fault conditin is cleared,
either automatically or by the operator/technician.
Fault information
Window 6. A maximum of 4 fault events may be displayed in this window.
All fault displays include: the nature of the fault event, and the time it
occurred; the time is relative to the UPS operating time.
Display faults Linear Plus
The various possible fault indicators are listed in the following table.
Fault
1.
2.
3.
4.
5.
6.
7 .
8.
9.
10.
11.
12.
13.
14.
Table 13: Fault indicators
EN-42
Cause
DC BUS fault
Inverter fault
Over temperature
Batt over volt.
Batt. mode overload
Output overload
Output short
Fan lock fault
Batt. Disconnect
Charger failure
ESD activated
Parallel fault
Internal fault
Output failure
User Handbook
CHLORIDE LINEAR Plus/RM
Corrective steps
Call customer service
Call customer service
Reduce load
Call customer service
Reduce load
Reduce load
Call customer service
Call customer service
Check battery connector
Call customer service
Call customer service
Call customer service
Call customer service
SU59802UM01, rev.3/ Last modified: 08/2005