CHLORIDE LINEAR Plus/RM
Setup parameter 53 of LCD Main menu
Parameter
1
2
3
4
5
Table 11: Battery setup parameter
Warning and fault indicators Linear Plus
Warning indicators
If a warning indication appears, the UPS continues to operate. The warning
message alternates with UPS mode once a second.
Display warnings
The various possible warning indicators are listed in the following table:
Warning
1.
2.
3.
4.
Table 12: Warning indicators
Fault indicators
If a fault occurs, the UPS automatically switches to BYPASS operating
mode, ONLY in case of a battery disconnect fault will the original operating
mode be maintained. The fault message alternates with UPS mode once a
second, the red fault LED illuminates on the control panel and the buzzer
sounds continuously. If a fault occurs, proceed as follow:
User Handbook SU59802UM01, rev.3/ Last modified: 08/2005
internal battery
quantity External
(x = integrated)
x
x
x
--
--
Cause
Batt under volt.
Utility failure
L2 or L3 failure
Over temp. 65
quantity 12V battery
battery cabinets
blocks in sum
--
1
2
1
2
Corrective steps
Check L2,L3 input fuse
Reduce load
Operating the Device
20
60
100
40
80
EN-41