Safety
Safety notices
Danger
Carefully read the following safety notices! Failure to observe the
instructions may endanger your life, your health, the reliability of your
device or the security of your data.
• Transport the unit only in suitable packaging (protected against jolts and
shocks).
• If the equipment is moved from a cold environment to the operating
room, condensation may occur. Before you switch on the equipment it
must be absolutely dry. An acclimatization period of at least two hours
is required.
• The equipment must be installed in accordance with the environmental
conditions specified in "Environmental conditions" on page EN-13 and
in Table 3 on page EN-16f.
• Linear Plus/RM devices are not intended to operate with isolated
neutral (IT systems). Neutral connector must be present and
connected to the UPS
• Even with all buttons in "OFF" (see chapter "Control panel Linear Plus"
on page EN-36) the device (UPS) is not isolated from the mains.
To isolate completely from the mains, the power cables must be
disconnected.
• In case of interruption of the mains voltage, the integrated battery
maintains the power supply to the user equipment.
• Lay all cables so that nobody can stand on them or trip over them.
When connecting the device to the power supply, follow the
instructions in the chapter "Installation" on page EN-16.
• Make sure that no objects (e.g. pins, necklaces, paper clips, etc.) get
inside the device.
• In emergencies (e.g. damaged case, controls or power cables,
penetration of liquids or foreign matter) switch off the device and
contact the appropriate customer service representative.
• Do not connect equipment that will overload the UPS (e.g. laser printers
or vacuum cleaners) or demand DC-current (e.g. half-wave rectifiers).
• When cleaning the unit, follow the instructions in the chapter
"Maintenance" on page EN-59.
• The sum of the leakage currents (protective conductor current) of the
UPS and the connected devices exceeds 3.5 mA for all ratings of the
UPS. Earth connection is essential before connecting supply.
• Data transmission lines should not be connected or disconnected
during a thunderstorm.
EN-4
User Handbook
CHLORIDE LINEAR Plus/RM
SU59802UM01, rev.3/ Last modified: 08/2005