Operating the Device
Self test
Lamp test
With the device connected to the mains, press the button "MENU", select
submenu "Control" and press "OK", select submenu "Turn UPS ON/OFF"
and press "OK", the LCD show "Turn UPS to BYPASS" then press "OK"
to off the inverter to Bypass-mode. Note that the load is not protected
against any mains disturbances or interruptions while the UPS is in Bypass-
mode. A single acoustic signal confirms the operation.
Battery test
Press the "MENU" button, select submenu "SETUP" and press "OK",
select submenu "BATT TEST" and press "OK".
A single acoustic signal confirms the operation and the load will be supplied
by the battery.
During the test an acoustic signal will be heard as though the device is
operating in battery mode.
If the test is successful, the "BATT" LED will stop flashing and the UPS will
return to "Line mode". If a battery malfunction is detected by the UPS, an
alarm will be displayed (see "Control and messages Linear Plus" on page
EN-36).
Lock of front panel
For easy operating the front panel can be turned to an oblique position. To
achive this please press the panel in the lower part and the panel will turn.
The panel is now fixed via a mechanical lock.
To release panel from this position loose the lock by softly pushing the
supporting rails upwards.
EN-54
User Handbook
CHLORIDE LINEAR Plus/RM
SU59802UM01, rev.3/ Last modified: 08/2005