Télécharger Imprimer la page

Chloride Power Protection Linear Plus Manuel D'utilisation page 45

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 73
CHLORIDE LINEAR Plus/RM
Parallel operation
Please refer to chapter "Paralleling UPS Devices" on page EN-55
Indication and Operating Elements Linear Plus RM
Panel Linear Plus RM
The OVERLOAD indicator (1) illuminates if the UPS is overloaded.
The LOAD LED strip (2) displays the load status of the UPS.
The BYPASS indicator (3) illuminates when the UPS delivers voltage
supplied from the mains supply via the bypass.
The INVERTER indicator (4) illuminates when the inverter is running.
The BATTERY LED chain (5) indicates the charging state of the battery
(normal operation).
The MAINS indicator (6) illuminates when normal mains voltage is present
at the UPS input.
The ALARM indicator (7) illuminates to indicate a UPS fault. An acoustical
warning signal is activated simultaneously; this signal is reset when the UPS
is switched off.
The
The
The inverter is activated by pressing the
of approx. 5 seconds, the BYPASS indicator extinguishes and the
INVERTER indicator illuminates.
Pressing the
bypass. UPS output voltage is present.
User Handbook SU59802UM01, rev.3/ Last modified: 08/2005
6
7
5
button switches the inverter Off and the bypass On.
button switches the inverter On (bypass Off).
button, blocks the inverter and switches the system to
1
4
2
3
button. Following a delay time
Operating the Device