Under the menu item FORCED PRE-BLEEDING you can choose if a specific biocide
metering procedure should be preceded by a bleeding, if the actual conductivity is above
the low bleeding threshold W- in a negative indication direction, or below the top bleeding
threshold W+ in a positive indication direction.
In the BIOCIDE METERING TIME the length of the biocide metering is determined in units
of seconds. The value parameter is effective from 0 to 9999 seconds. The bleeding
regulator is blocked during this time.
For TRACKING TIME, the tracking length after a biocide metering is determined in
seconds. The value parameter is effective from 0 to 9999 seconds. The bleeding regulator
is blocked during this time.
Under METERING TIME the time is set when the biocide metering is to be started. The
value parameter here is 00:00 to 23:59
The entry of values is done figure by figure.
1.
The access into the MEAS. PARAMETER SETTINGS and/or BIOCIDE
SETTINGS is done as described in chapter: 8.4.1, and/or.
Graph).
2.
If you are in the menu BIOCIDE SETTINGS 1 press the NEXT-Key to switch to level
BIOCIDE SETTINGS 2. The menu levels below these two areas are the same.
By pressing the „Enter-Key ↵" in BIOCIDE SETTINGS 1 or BIOCIDE SETTINGS 2
3.
you go to the menu item: PRECIRCULATION. In this menu you can increase and/or
lower the value be pressing
is accepted figure by figure. Pressing the key „Next" closes the process and changes
over to the menu level:
FORCED PRE-BLEEDING. If there are no changes desired in this level you switch
directly to BIOCIDE METERING TIME by pressing the „NEXT-Key". To switch the
preferred bleeding you can use either
After that press the NEXT-Key.
4.
The display changes to BIOCIDE METERING TIME.
If there are no changes desired in this level. In order to adjust the Biocide metering
time input the first of the four figures using the buttons
Then the second field will flash. The further figures must be inputted in an analogue
manner. Press NEXT to confirm.
5.
The display changes to TRACKING TIME.
If there are no changes desired in this levelMETERING CLOCK TIME by pressing
the NEXT Key. In order to adjust the tracking time input the first of the four figures
using the buttons
further figures must be inputted in an analogue manner. Press NEXT to confirm.
6.
The display changes to METERING CLOCK TIME.
If there are no changes desired in this levelMETERING DAY In order to adjust the
metering time input the first of the four figures using the buttons
Enter↵. Then the second field will flash. The further figures must be inputted in an
analogue manner. Press NEXT to confirm.
7.
The display changes to METERING DAY.
If there are no changes desired in this level BIOCIDE SETTINGS 1 or BIOCIDE
SETTINGS 2. In order to adjust the metering day select the corresponding day using
the buttons
8.
The display changes to the beginning at BIOCIDE SETTINGS 1 or
BIOCIDE SETTINGS 2.
417101555_CoolProtect.doc
or
. Then press Enter ↵. Then the second field will flash. The
or
or
. Press NEXT to confirm.
- 65 -
key. By pressing the „Enter-Key ↵" the set value
or
key to indicate Yes or No.
or
8.4.5
(Overview
. Then press Enter ↵ .
or
. Then press
Rev.: 08-06/10