Biocide Settings

The menu itemBIOCIDE SETTINGS (only for Art. No. 255155 & 255166) is only displayed if
NOTE
it was previously activated under the CONFIGURATION FUNCTIONS (see chapter:
Fig. 8.24
Overview
In the menus BIOCIDE SETTINGS 1 and BIOCIDE SETTINGS 2 you will find the settings
to adjust the parameters for the biocide control. These sub-menus are only available if it
was indicated prior in the configurations functions (see chapter 8).
Two times can be adjusted. Which time is adjusted is shown in the right edge of the first
line in the display. The parameters are identical for both times.
Under PRECIRCLUATION one can set the time, how long before a biocide metering the
relay to controling of the circulation has been activated.
The pre-circulation is only activated when at the time of the biocide metering there is no
release on the terminal 18/19.
417101555_CoolProtect.doc
- 64 -
8.5.3)
Rev.: 08-06/10