Measurement parameter settings

Fig. 8.13
Overview
The installation factor and the temperature coefficient Tkα can be adjusted via the
MEASUREMENT PARAMETER SETTINGS.
The access into the MEASUREMENT PARAMETER SETTINGS is done as described in
chapter: 8.1.
8.4.2.1 Installation Factor
The Installation Factor indicates the installation situation of the measuring cell. It is
variable between the values 0.50 and 2.00. The measuring value is multiplied by the
installation factor and displayed.
1. The access to the PARAMETER SETTINGS is done as described in chapter:
2. Pressing the „Enter-Key ↵" leads to the level: INSTALLATION FACTOR
Enter the first of the three digits by pressing this
Then press the Enter-Key↵. Then the second field will flash.
The following two digits are to be entered analogously.
Press the NEXT-Key to confirm.
The display changes to TEMP.COEFF..
If in the level INSTALLATION FACTOR no changes are desired, then it can be skipped
by pressing the „NEXT-Key" to go directly to TEMP.COEFF..