301IRFS Specifications

Gases Detected:
Sensing power requirements:
Sensing Technology:
Measurement Range:
Resolution:
Deadband:
Accuracy:
Response Time (T90):
Warmup time
Operating Environment:
Operating Temperature Range:
Operating Humidity Range:
Enclosure:
Size (HxWxD):
Weight:
The 301EM sensor LED has 2 functions. If the sensor is working properly,
the LED will blink according to the sensor addresses on the 301EM. In
that case, the LED will blink as shown:
Address 1 = The LED blinks 2 times during 2,8 seconds
Address 2 = The LED blinks 3 times during 2,8 seconds
Address 3 = The LED blinks 4 times during 2,8 seconds
Address 4 = The LED blinks 5 times during 2,8 seconds
Addresses 5 to 20 = The LED blinks once during 2,8 seconds
If the sensor is connected to a 301IRF, the LED will be on during 0,2
seconds and off during 2,6 seconds (blinking). If the sensor has a
problem (failsense), the LED will remain on.
R11, R12, R22, R114, R123, R125,
R134a, R404A, R407C, R410A, R507
8.5 - 12.5 Vdc, 1A@10Vdc Maximum
Infrared sensor
0-1000 ppm
1 ppm
20 ppm
±40 ppm @ 500 ppm and 25°C (77°F)
60 seconds
15 minutes
Indoor Use
0 to 40°C (32°F to 100°F)
0 to 95% RH (non-condensing)
ABS - Polycarbonate
10.2 x 28 x 6.3 cm
4.02" x 11.02" x 2.48"
0.603 kg (2.33 lbs)
301EM User Manual
Programming and Calibration
301IRFS Specifications