Specifications; Technical Specifications - Honeywell E3Point Manuel D'utilisation

Moniteur de gaz réseau
Masquer les pouces Voir aussi pour E3Point:
Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Technical Specifications

Input power:
Relay output :
Communication:
Operating environment: Commercial, indoor
Operating temperature
range:
Operating humidity
range:
Resolution:
Operating altitude:
Audible alarm:
Display:
Visual indicators:
Enclosure:
Dimensions (H x W x
D):
Certifications:
30

Specifications

24 VAC nominal, 17-27 VAC, 50/60 Hz, 0.35 A
24 VDC nominal, 20-38 VDC
1 DPDT relay, 5A @ 250 VAC
RS485 Modbus, BACnet MS/TP master
H
S, NO
, O
, Comb.: -40 to 50°C (-40°F to 122°F)
2
2
2
CO: -20 to 50°C (-4°F to 122°F)
Available option CO: -40 to 50°C (-40°F to 122°F)
15 to 90% RH non-condensing
CO = 1 ppm
O
= 0.1% vol.
2
H
S = 0.1 ppm,
2
NO
= 0.1 ppm
2
CH
, H
, C
H
= 0.1% LEL
4
2
3
8
Maximum 2000 m (6562 ft.)
>85 dB at 3 m (10 ft) minimum
8 character, 2 line LCD
Green LED: Power
Amber LED 1: Alarm/Fault
Amber LED 2: Transmission
Polycarbonate
20.56 x 14.90 x 6.72 cm (8.09 x 5.87 x 2.65 in.)
CSA C22.2 No. 61010-1,
UL61010
E
Point Network Gas Monitor User Manual
3