Modbus Registers Description
Number
21
Reading value
23
Divisor of reading value to obtain concentration
26
Sensor status
27
High temp warning status
34
The level at which Alarm A is triggered
35
Alarm A hysteresis offset (Alr A + Hyst A = level at which alarm
is deactivated)
36
The level at which Alarm B is triggered
37
Alarm B hysteresis offset (Alr B + Hyst B = level at which alarm
is deactivated)
38
The level at which Alarm C is triggered
39
Alarm C hysteresis offset (Alr C + Hyst C = level at which alarm
is deactivated)
61
Temperature High Level limit
66
Actual buzzer status (on or off)
70
Actual relay status (on or off)
The E³Point must not be written to as this could compromise the gas
detection function.
E
Point Network Gas Monitor User Manual
3
MODBUS
(RTU)
Description
37