Latch:
Keeps relays on even after an event has returned to normal.
Use the arrow keys to select Yes or No and press enter to
confirm the setting. Once a latched relay is activated, press
and hold a keypad button for 5 seconds to return relays to
their normal position (if trigger condition has resolved).
Failsafe:
Relays will be on in normal conditions but will de-energize
during a shutdown or when an alarm is triggered. In the
Failsafe menu, use the arrow keys to select either Yes or No
and press enter to confirm.
Because the network controller also controls failsafe settings, it will
perform the reverse of any locally configured settings.
Activate:
If the unit is configured with the Modbus or BACnet
communication protocol, these options are replaced with
Network. This menu option is inactive (no action can be
taken from this option) as this function is managed by the
network controller.
SetDelay: Allows users to specify a Before and After delay period for
relay alarm activation and deactivation.
In the SetDelay menu, use the arrow keys to display either
Before or After and press enter to select.
In the Before (or After) screen, use the arrow keys to increase
the delay in seconds (10 second increments, maximum of 360).
When the desired value is reached, press enter to confirm.
Press enter again to confirm the SetDelay (or use the arrow
keys to select No and cancel the procedure).
Programming Delay, Failsafe, and Latch functions directly on the
E
Point Network transmitter is NOT recommended, because local
3
settings will override network settings. These functions should
typically be programmed directly from the Network Control device.
E
Point Network Gas Monitor User Manual
3
SetDelay
Before
Before
000 sec
SetDelay
Yes
21