Password

Access to the programming menus is password protected. The Password
screen displays after enter is pressed.
Press the arrow key (up or down) to change the first letter to H.
Press the enter and use the arrow keys to change the second
letter to A.
Press enter to confirm the password and access the menus.
Use the arrow keys to scroll through the menu options.
In the event of an entry error, the unit reverts to normal display
mode. Restart the login process.

Network Menu

The Network menu contains several sub-menu options: Address,
BaudRate, BACnet ID, and Protocol. Use the arrow keys to scroll to the
desired option and press enter to select:
Address:
Use the arrow keys to increase or decrease the address
value (from 001 to 254 in Modbus or 1 to 127 in BACnet)
and press enter to confirm the desired address
BaudRate: Use the arrow keys to scroll through predefined baud rates
(4800, 9600, 19200, 38400, 57600, 76800) and press enter
to select.
Only 9600 baud is supported when the Modbus protocol is
selected.
BACnetID: Use the arrow keys to increase the value to the desired
BACnet ID and press enter to confirm.
Protocol:
Use the arrow keys to scroll to desired communication
rotocol (Modbus, 201T emu, BACnet) and press enter to
confirm.