Recommended Sensor Installation Heights
The installation heights recommended represent general guidelines.
Always confirm with local laws and regulations before proceeding, as
these take precedence over manufacturer's recommendations.
Detected Gas
CO
Carbon Monoxide
*NO2
Nitrogen Dioxide
CL2
Chlorine
H2S
Hydrogen Sulfide
O2
Oxygen
SO2
Sulfur Dioxide
R11
Refrigerants
R114
Refrigerants
R22
Refrigerants
R123
Refrigerants
R125
Refrigerants
R134A
Refrigerants
R404A
Refrigerants
R407C
Refrigerants
R410A
Refrigerants
R507
Refrigerants
COMB
Most combustibles are heavier than air, with the exception of methane,
hydrogen,ethylene and acetylene. Sensors for gases that are heavier than
air should be installed approximately 30 cm (1 foot) from the floor. For
combustibles that are lighter than air, sensors should be installed 30 cm (1
foot) from the ceiling, close to the potential leak source.
* May differ in certain applications. Hot NO
Relative Density
(air = 1)
0.968
1.58 (cold)
2.50
1.19
1.43
2.25
5.04
5.9
3.11
5.27
4.14
3.52
3.43
3.0
3.0
3.43
from exhaust systems is lighter than ambient air.
2
301EM User Manual
Installation Instructions
Wall Mount Installation
Installation Height
1 - 1.5 m (3 - 5 ft.) from floor
30 cm -1 m (1-3 ft.) from ceiling
30 cm (1 ft.) from floor
30 cm (1 ft.) from floor
1 - 1.5 m (3 - 5 ft.) from floor
30 cm (1 ft.) from floor
30 cm (1 ft.) from floor
30 cm (1 ft.) from floor
30 cm (1 ft.) from floor
30 cm (1 ft.) from floor
30 cm (1 ft.) from floor
30 cm (1 ft.) from floor
30 cm (1 ft.) from floor
30 cm (1 ft.) from floor
30 cm (1 ft.) from floor
30 cm (1 ft.) from floor
11